Mass flow rate for six pumps. Given in gallons per hour, converted to kg per second.
Figure 3 Pump system with input and output water paths.
Q=mC(Ti-Tf)
Model # 2

Determine the exit water temperature to verify that it is not lower than 23 C. Chose a pump that will give an exit water temperature of approxatmatly 23.5 C.
Given: Input energy, as determined from Model # 1. Intial temperature, heat capicity of water, mass flow rate for six different pumps. (210gph, 250gph, 450gph, 700gph, 750gph, 1200gph)

Assumptions: No heat loss in pipes, no mechanical energy losses in pipes.
The energy required for the system to be in steady state is 3.7 watts This is for an initial temperature of 27 C. These values will now be substituted into the next set of calculations to determine the mass flow rate and ultimatly the pump.
Energy ballance equation for the system
Resistance Totals: The Rleft corrospondes to the shell and insulation closest to the magnet bore and the Rright corrospondes the shells and insulation closest to the sample.
The calculations presented here were used to detemine system parameters for the design of the yeast cultavator. The system models were developed with the help of Dr. Haik, see Appendix M Meeting notes. Revisions may be done on these calculaions as the system developes.



Calculations by : James Sizemore



Approved and Checked by: Andrew Parry


Pump: 400 gph
Exit Water Temperature: 24.8 C
In the first set of the calculations a 400 pgh pump was selected. However, these calculations suggest a 250 to 350 gph pump. The pump chosen here will be the same as before, 400 gph pump, this is for these reasons:

1) Head loss will be introduced into the system by changing the relative height betwen the pump and the water jacket. When this system is used in the lab the pump may be required to set several feet below the water jacket. This will be used to lower the mass flow rate if necessary.
2) The over compensation of the pump size will allow for other losses that may occure in the system.
The mass flow rate determined from graph below was between 0.25082 kg/s and 0.37082 kg/s. This corresponds to 250 gph and 35 0 gph pumps. Some head loss will be expected, for this reason the pump with the greater mass flow rate will be selected. The exit water temperature used for the pump selection was between 23.46 C and 24.61 C.
The mass flow rate is varried to incorporate all the listed pumps above. This will allow the outlet temperture of the water to be graphed as a function of the mass flow rate.Mass flow is in SI, kg/s.
Given values: Heat capacity for water and intial inlet temperture for the supply water. The units are SI
L is the height of the system, X1-3 are the wall thicknesses, w's are the thicknesses for the two insulation layers and the water jacket. The r's are the values for the the raduii. The values are given in cm and are then conveted to meters for the calculations. See Figure 2 below.
Thermal conduction factors for alluminum and the insulation
Given temperatures for the sample, outside temperature, and the water sample.
Model # 1
Determine the amount of energy, in watts, needed to maintain the sample at 23 C. Determine the thickness of the insulation that will give optimal thermal resistance for the available area. The temperature of the water will be given an initial value close to that of the sample. This temperature will be checked for accuracy in Model # 2.
Given: The sample must remain at 23 C. The surrounding temperature is 8 C. The wall thickness are different for each cylinder. Initial trial value for the water temperature is 27 C. The height of the system (outer shell) is 25 cm.
Assumptions: Steady state, one dimensional heat flow, no convection on outside wall, the energy into the system is equal to the energy going to the sample and the outside wall, Qin = Qoutside + Qsample .
System Model:

Revision # 1: The calculations for the design needed to be changed due to material constraints. The intial calculations called for cylinders sizes that are not commonly manufactured. To get around this problem, cylinders with common sizes were chosen. The outter most cylinder in the first design and set of calculations was ellimanated because the size is not manufactured. This change is the main reason for this revision of the first set of calculations.

The system model was analyzed using energy balance. It was broken into two separate models. The first model was used to determine the energy supplied to the system Qin (watts) . The second model was used to determine the temperature of the the water after it leaves the water bath and the its' mass flow rate. The output temperature of the water should not be less than the temperature of the sample, 23 C.
Resistance equations for the cylindrical shells
Fi gure 2 Cut away of the Resistance network for one side
w ins1 x2 w water x3 w ins2 x4
Thermal resistance approach Q = Ti - Tf / Rtotal. The flow of energy, for this model, goes to the left and to the right. It was for this reason the model was analyzed in two parts, the left and the right. Each side having different thermal resistance due to their different geomertries.