| 
                 
                To study the decay of the jet velocity over distance, velocity 
                profiles of the jet were examined at specified locations 
                downstream of the vent exit.  A pitot-static probe was used to 
                obtain pressure measurements of the jet, because of its high 
                level of accuracy.  The fan assembly was placed at a designated 
                position and the pitot probe was placed directly at the center 
                of the vent exit.  The fan was turned on and the pressure 
                reading at the center of the vent exit was obtained by means of 
                a digital pressure meter.  The pitot probe was then moved 
                upwards in one centimeter increments and the corresponding 
                pressure readings were recorded.  This process was followed 
                until the upper boundary of the jet had been found.  The same 
                procedure was followed on the lower portion of the jet.  From 
                these pressure readings, the vertical velocity profile at the 
                exit of the vent was calculated.  Following the same procedures, 
                the vertical velocity profiles were calculated at one foot 
                intervals to a maximum distance of six feet.  A maximum distance 
                of six feet was chosen because it is the half scale distance to 
                the gunner position in the actual system.  This gunner position 
                is the primary target of the vent system.                
                  
                
                  
                
                  
                
                The analysis of the data obtained from the testing of the 
                Vehicle Movement System prototype produced the flow profile seen 
                in the figure below.  This figure shows how the air flow 
                developed over the testing distance.  Both the spread of 
                the jet and its relative velocity can be seen for the different 
                testing locations.  It can be seen in this figure that 
                there was a negative velocity obtained at the top of the vent 
                exit.  This is most likely due to a large turbulent 
                formation occurring from the sharp 90 degree turn of the duct 
                system.  This sharp turn was caused by a mass flow 
                separation, which introduced vortices into the air flow.   
                  
                
                  
                
                ** Note:  X-axis distance is not to scale** 
                  
                
                The theoretical spread rate of a plane rectangular jet is 0.11.  
                This theoretical spread rate was compared to the experimental 
                spread rate of the air flow from the vent.  From the spread rate 
                data collected from the experiment, the spread rate from the 
                vent of the prototype was 0.1181 for the flow above the 
                centerline velocity and 0.1083 below the centerline velocity.  
                The first two points were disregarded for the spread due to 
                their deviation from the rest of the points.  It is most likely 
                that this deviation is due to the large turbulent area found at 
                the top of the jet exit. 
                  
                
                   
                  
                
                As a result, the spread rate of the air flow from the prototype 
                is very similar to the expected theoretical data.  The flow 
                above the centerline velocity had a percent error of 7.36% and 
                the flow below the centerline velocity had a percent error of 
                1.54%.   
                  
                
                 From the test data the centerline velocity was plotted against 
                the distance from the vent exit.  The maximum velocity of the 
                air flow at the vent exit was 42.76 mph and it decreased to a 
                velocity of 15.79 mph six feet away from the vent exit.  This 
                can be seen in the figure below.   
                  
                  
                  
                 Theoretically, 
                the velocity of a turbulent plane jet decreases as the distance 
                from the jet increases at a rate of x-1/2, where x is 
                the half width of the jet.  The velocity vs. distance graph 
                shows that the velocity of the air flow decreases at a rate 
                similar to x-1/2.    
                  
                  
                  
                
                This graph is in non-dimensional units and can be scaled to any 
                size model.  Assuming that the actual system follows this model, 
                the centerline velocity at the vent exit should be approximately 
                115 mph in order for the target to attain 40 mph winds.  With no 
                losses, the average velocity exiting the actual vent system 
                would be 163 mph.  Assuming this is the centerline velocity, the 
                duct system must be at least 72% efficient for this fan to reach 
                the specified wind requirements.   
                  
                
                For a turbulent rectangular jet, the potential core vanishes at 
                a distance of about one diameter from the exit.  As the distance 
                from the vent increases, the theoretical profile of the velocity 
                develops a flatter shape.  Velocity profiles for the prototype 
                were developed at 0, 12, 24, 36, 48, 60, and 72 inches away from 
                the exit of the vent.  Based on the velocity profile data 
                collected from the experiment, which is referenced in Appendix 
                F, the velocity profiles developed a flatter shape as the 
                distance from the vent increased.  As a result, the velocity 
                profiles developed in the experiment followed the theoretical 
                trend.   
                  
                
                 It was also observed from the data collected that the 
                centerline height of the velocity drops as the distance from the 
                exit of vent increases.  The total drop in height of this 
                centerline velocity at a distance of six feet from the exit of 
                the vent, shown in Figure 6.6, was 26 cm. 
                  
                   
                  
                
                After analyzing the data acquired from the Vehicle Movement 
                System testing, conclusions were made in order to help improve 
                the originally proposed design.  The prototype model experienced 
                a mass flow separation prior to the exit of the vent.  This flow 
                separation led to a lower exit velocity and a non-uniform flow 
                profile.  Due to the fact that the prototype had a sharp 90 
                degree bend in the duct system, it is likely that it experienced 
                more turbulence than the actual design would.  The actual 
                designed system incorporated a rounded turn, which would help 
                reduce some of incurred turbulence.  In order to further reduce 
                the amount of turbulence created by the system, guide fins could 
                be added to help direct the flow around the 90 degree turn to 
                the vent exit.  Extending the length of the vent exit would also 
                help allow the flow to redevelop before it leaves the vent 
                exit.  A directional vent could also be added to the vent exit 
                in order to help direct the flow to the desired target location.  |